Bell Options
Complete the steps below to program the panel bell output functions:
In Bell Cutoff Time, enter the maximum number of minutes the Bell Output remains on.
Toggle Automatic Bell Test ON to allow the Bell Output to turn on for 2 seconds when all areas are armed from a keypad.
In Bell Output, enter the output/favorite number that follow’s the operation of the system’s Bell Output.
In Fire Bell Action, select one of the following options to configure the bell action for Fire type zones:
Steady
Pulse
Temporal 3 (default)
Temporal 4
None
In Burglary Bell Action, select one of the following options to configure the bell action for Burglary type zones:
Steady (default)
Pulse
Temporal 3
Temporal 4
None
In Supervisory Bell Action, select one of the following options to configure the bell action for Supervisory type zones:
Steady
Pulse
Temporal 3
Temporal 4
None (default)
In Panic Bell Action, select one of the following options to configure the bell action for Panic type zones:
Steady
Pulse
Temporal 3
Temporal 4
None (default)
In Emergency Bell Action, select one of the following options to configure the bell action for Emergency types zones:
Steady
Pulse
Temporal 3
Temporal 4
None (default)
In Auxiliary 1 Bell Action, select one of the following options to configure the bell action for Auxiliary 1 type zones.
Steady
Pulse
Temporal 3
Temporal 4
None (default)
In Auxiliary 2 Bell Action, select one of the following options to configure the bell action for Auxiliary 2 type zones.
Steady
Steady
Pulse
Temporal 3
Temporal 4
None (default)
In Carbon Monoxide (CO) Bell Action, select one of the following options to configure the bell action for CO type zones.
Steady
Pulse
Temporal 3
Temporal 4 (default)
None
Select the
(More) icon, then select Send Bell Options.