This programming menu allows you to program panel output options. The panel provides two Form C relays (1 and 2) and four switched ground (open collector) outputs numbered 3 to 6.
Expand the system up to 500 additional relay outputs using any LX-Bus on the panel, or multiple 716 Output Expander Modules. In addition, 45 wireless outputs are available when using the 1100XH Series wireless receiver. Refer to the XR150/XR550 Installation Guide for complete information.
Complete the following steps to program Output Options:
-
In Cutoff Output, enter which wired outputs (1-6) apply to the Output Cutoff Time.
-
In Output Cutoff Time, enter the number of minutes from 0-99 that the programmed Cutoff Output remains on before automatically turning off.
-
In Communication Fail Output, enter the output numbers that turn on when a communication failure condition occurs.
-
In Fire Alarm Output, enter the output numbers that turn on when a Fire or Fire Verify zone goes into alarm. The outputs turn off when all the zones restore to normal.
-
In Fire Trouble Output, enter the output numbers that turn on when a Fire or Fire Verify zone goes into trouble, or when a Supervisory zone goes into alarm or trouble. The outputs turn off when all the zones restore to normal.
-
In Panic Alarm Output, enter the output numbers that turn on when a Panic zone goes into alarm. The outputs turn off when all Panic zones are restored and a sensor reset is performed.
-
In Ambush Output, enter the output numbers that turn on when User Code 1 is entered at the keypad.
-
In Entry Delay Output, enter the output numbers that turn on when the Entry Delay begins. The outputs turn off when the area disarms or when the Entry Delay timer expires.
-
In Begin Exit Output, enter the output numbers that turn on when the Exit Delay begins. The outputs turn off when the area is armed or arming stops.
-
In End Exit Output, enter the output numbers that turn on when the Exit Delay ends. The outputs turn off when the system is disarmed.
-
In Ready Output, enter the output numbers that turn on when all disarmed zones are in a normal state. The outputs turn off when any zone is not normal.
-
In Disarmed Output, enter the output numbers that turn on when all areas are disarmed. The outputs turn off when an area is armed.
-
In Telephone Trouble Output, enter the output numbers that turn on when phone line trouble is detected.
-
In Late to Close Output, enter the output numbers that turn on if a closing schedule expires without all areas armed. The outputs turn off when all areas are armed, closing is extended, or the schedule is changed.
-
In Device Fail Output, enter the output numbers that turn on when a programmed keypad bus device does not respond to polling. The outputs turn off when the device responds or is deleted.
-
In Sensor Reset Output, enter the output numbers that turn on when a sensor reset is performed. The outputs turn off 5 seconds after being turned on.
-
In Closing Wait Output, enter the output numbers that turn on if the receiver acknowledges the Closing Wait operation (if programmed). The outputs turn off 4 seconds later.
-
In Arm-Alarm Output, enter the output numbers that turn on steady if any area is armed. Alarms cause the output to pulse until 3 minutes after disarming.
-
In Supervisory Alarm Output, enter the output numbers that turn on a Supervisory zone is in alarm. The outputs turn off when all Supervisory zones are restored to normal.
-
In Armed Home Output, enter the output numbers that turn on when the system is armed home. Alarms cause the output to pulse until 3 minutes after disarming.
-
In Armed Away Output, enter the output numbers that turn on when the system is armed away. Alarms cause the output to pulse until 3 minutes after disarming.
-
In Armed Sleep Output, enter the output numbers that turn on when the system is armed sleep. Alarms cause the output to pulse until 3 minutes after disarming.
-
In Heat Saver Temperature, enter the temperature (F°) that sends to all Z-Wave thermostats when the system is armed All or Away. When the system is disarmed, the thermostats return to the previous temperatures.
-
In Cool Saver Temperature, enter the temperature (F°) that sends to all Z-Wave thermostats when the system is armed All or Away. When the system is disarmed, the thermostats return to the previous temperatures.
-
In Carbon Monoxide Output, enter the output numbers that turn on when a Carbon Monoxide zone is in alarm. The output turns off when an area is armed.
-
In Lockdown Output, enter the output numbers that turn on during a lockdown. The outputs turn off when an authorized user ends the lockdown.
-
In Zone Monitor Output, enter the output numbers that turn on when a zone trip sounds the Zone Monitor. The outputs turn off 2 seconds later.
-
Select the
(More) icon, then select Send Output Options.